Provide a roof condition report to AS 1562.1 AS 1562.3 And SA HB 39 2015 The installation code for metal roofing and walling. Provide recommendations to extend longevity.
Inspection Site Gallery
Findings & Recommendations Report For Oxenford Roof Inspection
Screw missing, also note the flat metal is loose and has no fasteners, this is the same for every gable end.
Sheets not turned down as per manufacturer’s installation instructions. Upper roof pitch is 0-degrees. Lower roof has been turned down.
Minor swarf detected across all areas of the roof.
Foot traffic damage was widespread across the lower section of the split pitch with one severe dent in the valley.
Appears to be some thermal movement happening at these transition flashing connections. It would be prudent to monitor these to ensure flashing joins do not separate.
Insufficient fasteners in tray flashings, non-compliant to SA HB 39 refer 7.2.
Dektites are blocking the pans with potential for future ponding corrosion.
Chimney flashings incomplete, both the upper and lower roof areas.
Sheet underlaps are not cut back with potential for ingress from water draw back.
Flashing connection here is the only one not over-sealed and is non-compliant to SA HB 39 refer 5.8.1, no under seal has taken place, it may be prudent to ensure all flashing joins have been under-sealed correctly.
For more information about our roof inspection service or to book please visit our contact page to find out how to get in touch with us.